These devices can detect problems and provide information needed to improve efficiency and save money.
Endress+Hauser
08/07/2017
Companies incur thousands, if not millions, of dollars in maintenance costs to keep their pumping systems in good health. Predictive maintenance is one of the best ways to cut pump operating costs. One effective predictive maintenance technique uses an electronic differential pressure transmitter to not only monitor instantaneous pump performance, but also to identify issues related to pump health and efficiency.
Figure 1. The BEP is 70 to 85 percent of the maximum differential pressure between the suction and discharge pressure. (Images and graphics courtesy of Endress+Hauser)
Monitoring Differential Pressure
All pumps perform best when they are at, or very close to, their best efficiency point (BEP) (see Figure 1). The BEP is defined by the manufacturer on its pump curve and is typically 70 to 85 percent of the shut-off head or maximum differential pressure between the suction and discharge. Operating at the BEP is the single most important aspect for prolonging pump life and cutting maintenance time and costs. An electronic differential pressure (EdP) transmitter is well suited for monitoring the performance of a pump in applications where continuous operation is critical, such as cooling tower systems or aeration pumps in wastewater treatment.Image 1. An EdP transmitter monitors a pump’s suction and discharge pressure.
An EdP transmitter primarily measures level and differential pressure in tanks, distillation columns or cooling towers, but it can also be used in pumping systems (see Image 1).
An EdP transmitter can monitor the suction and discharge pressure (the differential pressure) of a pump. Too high or too low suction and discharge pressures can cause various pump issues such as cavitation, loss of flow, mechanical failure, vibration issues, excessive noise, and bearing and sealing wear.
The EdP transmitter outputs values for suction, discharge and differential pressure, and other useful values. An EdP transmitter can also monitor absolute pressure at each of the two sensing points.
High and low alarms can be set for any of the monitored values. The EdP has a 4-20mA HART output for connection to an automation system, such as a programmable logic controller (PLC) or a distributed control system (DCS).
The DP or gauge value from the EdP can be used to set alarms, which in turn help monitor problems such as cavitation.
For example, cavitation occurs if the pressure falls below a liquid’s vapor pressure in the impeller or if air entrainment occurs. Monitoring the discharge pressure and comparing it to a table of correct pressures at the automation system will reveal cavitation. Monitoring pressure in the suction line can indicate problems such as leaks or a clogged valve or strainer. If suction pressure drops below preset limits, the EdP transmitter will send an alarm.
Setting the Right Flow Rate
Incorrect flow rate settings are one of the typical causes of inefficient pump operation. Following is an example of how to use the EdP to set the right flow rate. For a given pump curve, first note:Figure 2. Pump curve for determining flow rate of a pump with a 10-inch impeller.
- impeller size
- rated horsepower
- impeller speed
- expected flow at BEP
Figure 3. Pump curve for monitoring total head.
To increase efficiency and run this pump at the same total head, the flow rate needs to be increased to 55 gpm (right-most red dotted line in Figure 3) so that the intersection with the 85 percent efficiency curve will be at point B. The users should set high and low alarms on the EdP output to keep the DP tightly controlled while increasing the flow rate.
If the pump doesn’t generate 120 feet total head at the 55 gpm flow rate, this could be your first indication of an operational or mechanical issue. Check the suction pressure and ensure it is greater than NPSHr. Check the discharge pressure and calculate the HP generated and verify it matches the listed HP on the pump curve for the operating flow rate.
Monitoring Total Head
Assume 55 gpm is the operating flow rate for a 6 HP pump with an 8-inch impeller. The expected intersection on the performance curve for this pump would be point A (see Figure 3). The corresponding expected total head on the Y-axis would be 65 feet.Image 2. An EdP differential pressure transmitter mounted across a pump.
The EdP transmitter sends its outputs to an automation system that has control logic and calculations to convert the transmitter data to total head. The automation system compares the EdP transmitter outputs to the expected total head—65 feet of water in this case—and adjusts pump speed accordingly.
This alters the pump speed to maintain the pump at BEP, which is 70 percent according to the manufacturer’s pump curve.
If higher pump efficiency is desired, the pump must be run at a higher speed, or a larger impeller diameter needs to be used.
With a known flow rate, different impeller sizes can be used to arrive at a desired total head and corresponding efficiency. Referring to Figure 3, if 55 gpm is the known flow rate, then an 8-inch impeller can be used to achieve 70 percent efficiency. If a higher efficiency is desired, then a 10-inch impeller can be used to achieve an efficiency of 75 percent, and a 12-inch impeller would achieve 85 percent. The corresponding total head would then be 100 feet of water.
Figure 4. Increasing efficiency from 70 to 75 percent on five pumps can save over $12,000 per year.